Flue Gas Analyzer - Insitu Type
T-MGA-IN-1000

Flue Gas Analyzer - Insitu Type

T-MGA-IN-1000 Flue Gas Analyzer is a highly integrated single-flange gas monitoring equipment, of which, core detection module adopts Tunable Diode Laser Absorption Spectroscopy (TDLAS), Differential Optical Absorption Spectroscopy (DOAS) gas absorption technology and Zirconia with independent intellectual property rights. The specially designed measuring cell effectively improves optical path length for gas absorption, which can measure trace gas accurately inside pipeline T-MGA-IN-1000 can be widely applied in online gas monitoring occasions including denitrification device, boiler flue and exhaust detection, etc. One equipment can realize online monitoring for multiple gas components, such as CO,CO2, SO2, NO, NO2,O2 etc.

Related Products

CEMS

Filter element can be easily disassembled and replaced 

Adopt single-flange design with high integration and easy installation 

With high-temperature flowmeter, user can observe flow during equipment operation 

Sampling measurement is free from interference of pipeline deformation, high dust and other working condition change, with strong adaptability 

The whole gas path is equipped with high-temperature heat tracing and regular auto purge to prevent dust and crystal like salt from blocking the equipment, less maintenance 

Suitable in high dust load application (up to 50gm/m3)

Boiler Stack Emission Monitoring

Industrial Process Monitoring

Fgd (Flue Gas Desulfurization)

Boiler Control

Coal Mill And Coal Bin

Cement Rotary Kiln

Integrated Iron & Steel Coke Oven Plant, Blast Furnace & Cupola Foundry

Incinerator Stack

              TDLAS technical Index

            DOAS Technical Index

Principle

TDLAS

Principle

DOAS

Component

CO:0-1000ppm,CO2:0-25% (TDLAS) ,

O2: 0-25% (Zirconia/TDLAS) 

 (Higher range can be customized)

Component

SO2:0-1000ppm,N0:0-1000ppm,NO2:0-1000ppm,

NOX:0-1000 ppm (Higher range can be customized)

Accuracy

±2% FS

Accuracy

±2% FS

Repeatability

±2% FS

Repeatability

±2% FS

Zero drift

±2% FS/30D

Zero drift

±2% FS/30D

Span drift 

±2% FS/30D

Span drift 

±2% FS/30D

Parameter

Description 

Working power

230±10% ,50Hz,600W

Instrument Air supply

4-5 bar ,oil-free,water-free and dust-free Air

Response time

T90<= 20s (double Modules)

Analog output

5 x 4-20mA output (depend on gas parameter)

Relay output

4 x relay output

Digital output

1 x RS485 output/ Profibus 

Ambient temperature

-20 deg. C ~ 60 deg. C

Process temp. 

below 600 deg. C

Ambient humidity

<=90% ,non condensing

Dimension

448mm(L) * 420mm(W) * 240mm(D)

Weight

About 45kg